54 Use of fire doors in buildings - General requirement of fire doors in individual occupancies 3.4.5.6 - Vertical Opening in between floors a) Shall have a clear opening height of 2100mm if it is in the exit pathway (means of egress) b) Shall have minimum 120minutes fire rated door 3.4.6.3 - Substations / transformers a) Air-conditioned MV panel room to be provided in basement or ground floor. b) It should be provided with fire rated walls and doors of minimum 120minutes.