55 Use of fire doors in buildings - General requirement of fire doors in individual occupancies 3.4.6.4 - Standby supplies like DG room if it is installed within the building it should have the wall and door of minimum 120minutes rating. 3.4.8.1 - Air conditioning, heating and mechanical ventilation a) Battery rooms shall also have 120minutes segregation as a compartment 3.4.8.2 - Air handling unit a) 3.4.8.2.1 - The requirement is more for smoke control doors b) 3.4.8.2.2 – walls and doors of shafts, ducts, and room shall be 120min fire rating c) Smoke and fire dampers to be provided in each shaft zone and floor wise.